6. Maintenance and Troubleshooting
6.1 Maintenance Intervals
TheENERVEXGreaseFanisdesignedforprolongeduse.Fordirtyorgrease-ladenexhaust,inspectthe
impellerafter(3)monthsandsetupaperiodicinspectionbasedonthesendings.Cleanasrequired.
The fan motors are equipped with permanently lubricated sealed ball bearings. They require no lubrication.
6.2 Cleaning
Warning: Do not open the motor housing unless power to the grease fan has been disconnected
Loosen the two Phillips screws in the front of the unit.
Tilt the top of the fan by lifting on the handle. Make
sure the locking arm holds the top of the fan
before letting go.
If necessary, use grease remover and a high-pressure
cleaner to clean the impeller and the inside fan
base.
A scraper may also be used.
6.3 Troubleshooting
!
Caution: Never place hands or ngers
on top of fan base when closing.
!
Problem Possible Cause What to do
The fan is not operating. No power to the fan. Checkthepowersupplywiresinthejunctionboxbythefan.
Check the circuit breaker.
Check that the fan is actually turned ON.
The fan is not running
at full speed and/or is
humming.
The capacitor is improperly
connected or not connected at all
(single-phase fans only).
Checktheconnectionsinsidethejunctionbox.Thecapacitor
must be installed according to wiring diagram.
The fan is rotating
backwards (RSV 400/450
only).
Phase sequence in the power to
the fan is reversed.
Swaptwophasesinthejunctionbox.
The fan is vibrating
vigorously.
The motor shaft is damaged. Turn the power off immediately. Open the fan and check if the
shaft is straight. If not, contact ENERVEX.
The fan is noisy. A transportation device has not
been removed.
Foreign matter is stuck in the fan.
A ball bearing is damaged.
Remove the transportation device.
Turn off the power and remove the foreign article.
Turn off the power. Wait for the motor to stop revolving. Spin
the wheel and listen for any grinding noise from the motor. If
necessary, replace bearing.
The fan stops in the
middleofaringcycle.
The motor is overheating. Checktheuegastemperaturebelowthefan.Thetemperature
shouldnotexceed400°Fduringcontinuousoperation.Call
ENERVEX.